Analog Modules
4-73
Programmable Logic Controllers S7-300 Module Data
A5E00105505-03
Diagnostic messages of the analog output modules
The table below gives an overview of the diagnostic messages for the analog
output modules.
Table 4-47 Diagnostics Messages of the Analog Output Modules
Diagnostics Message
LED Diagnostics Ef-
fective for
Parameters can
be assigned
External auxiliary supply missing SF Module No
Configuring/parameter assignment
error
SF
Channel Yes
Short-circuit to M SF Channel Yes
Wire-break SF Channel Yes
Note
A prerequisite for detecting the errors indicated by programmable diagnostic
messages is that you have assigned parameters to the analog module accordingly
in STEP 7.
Causes of errors and remedial measures for analog input modules
Table 4-48 Diagnostics Messages of the Analog Input Modules, Causes of Errors and
Remedial Measures
Diagnostics
Message
Possible Error Cause Remedy
External load voltage
missing
Load voltage L+ of module missing Feed supply L+
Configuring/paramete
r
assignment error
Illegal parameters transferred to
module
Check measuring range module
assignment error module
Reassign module parameter
Common-mode error Potential difference U
CM
between
the inputs (M–) and reference
potential of measuring circuit (M
ANA
)
too high
Connect M– with M
ANA
Wire-break Resistance too high in the sensor
connection
Use different type of sensor or
connection, e.g. use conductors with a
larger cross-sectional core area
Open circuit between module and
sensor
Close circuit
Channel not connected (open) Disable channel group (“measuring
procedure” parameter
Connect channel

Table of Contents

Other manuals for Siemens SIMATIC S7-300 Module data

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMATIC S7-300 Module data and is the answer not in the manual?

Siemens SIMATIC S7-300 Module data Specifications

General IconGeneral
SeriesS7-300
ManufacturerSiemens
Protection ClassIP20
SystemSIMATIC S7-300
Digital InputsVaries by module
Digital OutputsVaries by module
Analog InputsVaries by module
Analog OutputsVaries by module
Central Processing UnitVaries by CPU model
Supply Voltage24V DC or 120/230V AC
CPU TypeVaries (e.g., CPU 312, CPU 315, etc.)
MemoryVaries by CPU model
Communication InterfacesMPI, PROFIBUS
Programming LanguagesLAD, FBD, STL, SCL, GRAPH
Operating Temperature0°C to 60°C
Storage Temperature-40°C to 70°C
Relative Humidity10% to 95% (non-condensing)

Related product manuals