Analog Modules
4-94
Programmable Logic Controllers S7-300 Module Data
A5E00105505-03
Scan time of the module
In 4-channel mode, the channel conversion time including communication time of
the SM 331; AI 8 x 16 bits is 10 ms. As the module does not switch over between
the channels in a group, the channel scan time and the module
scan time are the same: 10 ms.
4.19.4 Measuring Methods and Measuring Ranges of the SM 331;
AI 8 x16 bits
Measuring Methods
You can set the following measuring methods for the input channels:
Voltage measurement
Current measurement (4-wire transmitter)
You perform the setting with the “measuring method” parameter in STEP 7.
Unused Channels
Set the “measuring method” parameter for unused channels to “disabled”. In this
way you shorten the scan time of the module.
Since configured inputs can remain unused because of the channel group
generation, you must take note of the following special characteristics of these
inputs to enable the diagnostic functions on the used channels.
Measuring range 1 to 5 V: Connect the unused input in parallel with a used
input of the same channel group.
Current measurement, 4 to 20 mA: Connect the unused input in series with
an input of the same channel group. Ensure that a current sense resistor is
connected for each active and unused channel.
Other ranges: Short the positive to the negative input of the channel.

Table of Contents

Other manuals for Siemens SIMATIC S7-300 Module data

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMATIC S7-300 Module data and is the answer not in the manual?

Siemens SIMATIC S7-300 Module data Specifications

General IconGeneral
SeriesS7-300
ManufacturerSiemens
Protection ClassIP20
SystemSIMATIC S7-300
Digital InputsVaries by module
Digital OutputsVaries by module
Analog InputsVaries by module
Analog OutputsVaries by module
Central Processing UnitVaries by CPU model
Supply Voltage24V DC or 120/230V AC
CPU TypeVaries (e.g., CPU 312, CPU 315, etc.)
MemoryVaries by CPU model
Communication InterfacesMPI, PROFIBUS
Programming LanguagesLAD, FBD, STL, SCL, GRAPH
Operating Temperature0°C to 60°C
Storage Temperature-40°C to 70°C
Relative Humidity10% to 95% (non-condensing)

Related product manuals