Parameter Sets for Signal Modules
A-25
Programmable Logic Controllers S7-300 Module Data
A5E00105505-03
Measuring methods and measuring ranges of the SM 331; AI 8 x TC
The table below contains all the measuring methods and measuring ranges of the
module and its codes. You must enter these codes in the corresponding bytes of
data record 128 (refer to Figure A-3).
Table A-16 Codes for the Measuring Ranges of the SM 331; AI 8 x TC
Measuring Method
Code Measuring
Range
Code
Deactivated 2#0000 Deactivated 2#0000
Thermocouple, linear,
reference temperature 0 °C
2#1010 B
N
E
R
S
J
L
T
K
U
C
2#0000
2#0001
2#0010
2#0011
2#0100
2#0101
2#0110
2#0111
2#1000
2#1001
2#1010
Thermocouple, linear,
reference temperature 50 °C
2#1011 B
N
E
R
S
J
L
T
K
U
C
2#0000
2#0001
2#0010
2#0011
2#0100
2#0101
2#0110
2#0111
2#1000
2#1001
2#1010
Thermocouple, linear, internal comparison 2#1101 B
N
E
R
S
J
L
T
K
U
C
2#0000
2#0001
2#0010
2#0011
2#0100
2#0101
2#0110
2#0111
2#1000
2#1001
2#1010
Thermocouple, linear, external comparison 2#1110 B
N
E
R
S
J
L
T
K
U
C
2#0000
2#0001
2#0010
2#0011
2#0100
2#0101
2#0110
2#0111
2#1000
2#1001
2#1010

Table of Contents

Other manuals for Siemens SIMATIC S7-300 Module data

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMATIC S7-300 Module data and is the answer not in the manual?

Siemens SIMATIC S7-300 Module data Specifications

General IconGeneral
SeriesS7-300
ManufacturerSiemens
Protection ClassIP20
SystemSIMATIC S7-300
Digital InputsVaries by module
Digital OutputsVaries by module
Analog InputsVaries by module
Analog OutputsVaries by module
Central Processing UnitVaries by CPU model
Supply Voltage24V DC or 120/230V AC
CPU TypeVaries (e.g., CPU 312, CPU 315, etc.)
MemoryVaries by CPU model
Communication InterfacesMPI, PROFIBUS
Programming LanguagesLAD, FBD, STL, SCL, GRAPH
Operating Temperature0°C to 60°C
Storage Temperature-40°C to 70°C
Relative Humidity10% to 95% (non-condensing)

Related product manuals