EasyManuals Logo

Siemens SIMATIC S7-300 Module data Reference Manual

Siemens SIMATIC S7-300 Module data
574 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #132 background imageLoading...
Page #132 background image
Digital Modules
3-48
Programmable Logic Controllers S7-300 Module Data
A5E00105505-03
Terminal Assignment of the SM 322; DO 32 x 24 VDC/ 0.5 A
Dimensions and Weight
Dimensions W x H x D
(in millimeters)
40 x 125 x 117
Weight Approx. 260 g
Data for Specific Module
Supports clocked
operation
No
Number of outputs 32
Length of cable
Unshielded
Shielded
max. 600 m
max. 1000 m
Voltages, Currents, Potentials
Rated load voltage L+ 24 VDC
Total current of the outputs
(per group)
Horizontal configuration
Up to 40 C
Up to 60 C
max. 4 A
max. 3 A
Vertical configuration
Up to 40 C max. 2 A
Isolation
Between channels and
backplane bus
Yes
Between the channels
In groups of
Yes
8
Permitted potential difference
Between the different
circuits
75 VDC / 60 VAC
Insulation tested with 500 VDC
Current consumption
From the backplane bus
From load voltage L +
(without load)
max. 110 mA
max. 160 mA
Power dissipation of the module typ. 6.6 W
Status, Interrupts, Diagnostics
Status display Green LED per channel
Interrupts None
Diagnostic functions None
Data for Selecting an Actuator
Output voltage
At signal “1” min. L + (–0.8 V)
Output current
At signal “1”
Rated value
Permitted range
0.5 A
5 mA to 0.6 A
At signal “0”
(leakage current)
max. 0.5 mA
Output delay (for resistive load)
From “ 0” to “1” max. 100 s
At “1” to “0” max. 500 s
Load resistor range 48 to 4 k
Lamp load max. 5 W
Parallel connection of 2
outputs
For redundant triggering of
a load
Possible (only outputs
of the same group)
To increase performance Not possible
Triggering a digital input Possible
Switch rate
For resistive load max. 100 Hz
Inductive loads
according to IEC 947-5-1,
DC 13
max. 0.5 Hz
For lamp load max. 10 Hz
Limit (internal) of the inductive
circuit interruption voltage up
L + (–53 V), typ.
Short-circuit protection of the
output
Yes, electronic
Threshold on 1 A, typ.

Table of Contents

Other manuals for Siemens SIMATIC S7-300 Module data

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMATIC S7-300 Module data and is the answer not in the manual?

Siemens SIMATIC S7-300 Module data Specifications

General IconGeneral
SeriesS7-300
ManufacturerSiemens
Protection ClassIP20
SystemSIMATIC S7-300
Digital InputsVaries by module
Digital OutputsVaries by module
Analog InputsVaries by module
Analog OutputsVaries by module
Central Processing UnitVaries by CPU model
Supply Voltage24V DC or 120/230V AC
CPU TypeVaries (e.g., CPU 312, CPU 315, etc.)
MemoryVaries by CPU model
Communication InterfacesMPI, PROFIBUS
Programming LanguagesLAD, FBD, STL, SCL, GRAPH
Operating Temperature0°C to 60°C
Storage Temperature-40°C to 70°C
Relative Humidity10% to 95% (non-condensing)