General Technical Specifications
1-16
Programmable Logic Controllers S7-300 Module Data
A5E00105505-03
1.8 Mechanical and Climatic Ambient Conditions for the Operation
of SIPLUS S7-300 Modules
Ambient mechanical conditions
Operating category: according to IEC 721 3-3, Class 3M4.
Ambient mechanical conditions test
The following table contains important information on the type and scope of tests
for ambient mechanical conditions of SIPLUS S7-300 modules.
Table 1-11 SIPLUS S7-300 Modules Ambient Mechanical Conditions Test
Test ...
Test Standard Remarks
Vibrations Vibration test according to
IEC 6008 Part 2-6 (sinusoidal)
Type of oscillation: frequency sweeps with a rate of
change of
1 octave/minute.
5 Hz f 9 Hz, constant amplitude of 3.5 mm
9 Hz f 150 Hz, constant acceleration of 1 g
oscillation period: 10 frequency sweeps per axis in
each of three axes perpendicular to each other
Shock Shock test according to IEC 6008
Part 2-27
Type of shock: half-sine
severity of shock: 15 g peak value, 11 ms duration
Direction of shock: 3 shocks each in the +/–
direction in each of three axes perpendicular to
each other

Table of Contents

Other manuals for Siemens SIMATIC S7-300 Module data

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMATIC S7-300 Module data and is the answer not in the manual?

Siemens SIMATIC S7-300 Module data Specifications

General IconGeneral
SeriesS7-300
ManufacturerSiemens
Protection ClassIP20
SystemSIMATIC S7-300
Digital InputsVaries by module
Digital OutputsVaries by module
Analog InputsVaries by module
Analog OutputsVaries by module
Central Processing UnitVaries by CPU model
Supply Voltage24V DC or 120/230V AC
CPU TypeVaries (e.g., CPU 312, CPU 315, etc.)
MemoryVaries by CPU model
Communication InterfacesMPI, PROFIBUS
Programming LanguagesLAD, FBD, STL, SCL, GRAPH
Operating Temperature0°C to 60°C
Storage Temperature-40°C to 70°C
Relative Humidity10% to 95% (non-condensing)