Analog Modules
4-89
Programmable Logic Controllers S7-300 Module Data
A5E00105505-03
Data for selecting a sensor
Input range (rated values) /
input resistance
Voltage $ 5 V / 2 M
1 to 5 V / 2 M
$ 10 V / 2 M
Current 0 to 20 mA / 250
4 to 20 mA / 250
$20 mA / 250
Maximum input voltage for
voltage input
(destruction limit)
35 VDC continuous;
75 VDC for max. 1 s
(duty factor 1:20)
Maximum input current for
current input
(destruction limit)
40 mA
Connection of the sensor
For measuring voltage Possible
For measuring current
As two-wire transmitter Possible with separate
supply for the
transmitter
As four-wire transmitter Possible
1)
Interference frequency for 4-channel mode is “All”
2)
Interference frequencies 50/60/400 Hz are designated as
“All”
3)
Series-mode rejection for
8-channel mode is reduced as follows:
50 Hz > 70 dB
60 Hz > 70 dB
400 Hz > 80 dB
50/60/400 Hz > 90 dB
4.19.1 Commissioning the SM 331; AI 8 x 16 bits
The mode of operation of the SM 331; AI 8 x 16 bits is set with STEP 7.
Parameter
You will find a description of the general procedure for parameterizing the SM 331;
AI 8 x 16 bits, in section 4.7.
Parameterization restrictions when using the analog input module SM 331;
AI 8 x 16 bits with PROFIBUS masters that only support DPV0.
When you use the isolated analog input module SM 331; AI 8 16 bits in an
ET200M PROFIBUS slave system with a PROFIBUS master which is not an S7
master, certain parameters are not permitted. Masters that are not S7 masters do
not support hardware interrupts. So all the parameters associated with these
functions are deactivated. The deactivated parameters are hardware interrupt
enable, hardware restrictions and end-of-scan-cycle interrupt enable. All the other
parameters are permitted.

Table of Contents

Other manuals for Siemens SIMATIC S7-300 Module data

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMATIC S7-300 Module data and is the answer not in the manual?

Siemens SIMATIC S7-300 Module data Specifications

General IconGeneral
SeriesS7-300
ManufacturerSiemens
Protection ClassIP20
SystemSIMATIC S7-300
Digital InputsVaries by module
Digital OutputsVaries by module
Analog InputsVaries by module
Analog OutputsVaries by module
Central Processing UnitVaries by CPU model
Supply Voltage24V DC or 120/230V AC
CPU TypeVaries (e.g., CPU 312, CPU 315, etc.)
MemoryVaries by CPU model
Communication InterfacesMPI, PROFIBUS
Programming LanguagesLAD, FBD, STL, SCL, GRAPH
Operating Temperature0°C to 60°C
Storage Temperature-40°C to 70°C
Relative Humidity10% to 95% (non-condensing)

Related product manuals