EasyManua.ls Logo

Siemens SIMATIC S7-300 Module data - Analog Value Representation for RTD Resistance Temperature Detectors Ni100, 120, 200, 500, 1000, LG-Ni 1000

Siemens SIMATIC S7-300 Module data
574 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Analog Modules
4-17
Programmable Logic Controllers S7-300 Module Data
A5E00105505-03
Analog value representation for RTD Resistance Temperature Detectors Ni x00
standard
Table 4-18 Analog value representation for RTD Resistance Temperature Detectors Ni100, 120, 200, 500,
1000, LG-Ni 1000
Ni x00
standard
in C
Units Ni x00
standard
in F
Units Ni x00
standard
in K
Units
standard
in 5C
(1 digit =
0.15C)
decimal hexa-
decimal
standard
in 5F
(1 digit =
0.1 5F)
decimal hexa-
decimal
standard
in K
(1 digit =
0.1 K)
decimal hexa-
decimal
Range
>295.0 32767 7FFF
H
>563.0 32767 7FFF
H
>568.2 32767 7FFF
H
Overflow
295.0
:
250.1
2950
:
2501
B86
H
:
9C5
H
563.0
:
482.1
5630
:
4821
15FE
H
:
12D5
H
568.2
:
523.3
5682
:
5233
1632
H
:
1471
H
Overrange
250.0
:
–60.0
2500
:
–600
9C4
H
:
FDA8
H
482.0
:
–76.0
4820
:
–760
12D4
H
:
FD08
H
523.2
:
213.2
5232
:
2132
1470
H
:
854
H
Rated
range
–60.1
:
–105.0
–601
:
–1050
FDA7
H
:
FBE6
H
–76.1
:
–157.0
–761
:
–1570
FD07
H
:
F9DE
H
213.1
:
168.2
2131
:
1682
853
H
:
692
H
Underrange
< –105.0 –32768 8000
H
< –157.0 –32768 8000
H
<168.2 32768 8000
H
Underflow
Analog value representation for RTD Resistance Temperature Detectors Ni x00
climate
Table 4-19 Analog value representation for RTD Resistance Temperature Detectors Ni 100, 120, 200,
500, 1000, LG-Ni 1000
Ni x00
climate
in C
Units Ni x00
climate
in F
Units
climate
in 5C
(1 digit =
0.015C)
decimal hexa-
decimal
climate
in 5F
(1 digit =
0.01 5F)
decimal hexa-
decimal
Range
> 295.00 32767 7FFF
H
>325.11 32767 7FFF
H
Overflow
295.00
:
250.01
29500
:
25001
733C
H
:
61A9
H
327.66
:
280.01
32766
:
28001
7FFE
H
:
6D61
H
Overrange
250.00
:
–60.00
25000
:
–6000
61A8
H
:
E890
H
280.00
:
–76.00
28000
:
–7600
6D60
H
:
E250
H
Rated range
–60.01
:
–105.00
–6001
:
–10500
E88F
H
:
D6FC
H
–76.01
:
–157.00
–7601
:
–15700
E24F
H
:
C2AC
H
Underrange
< –105.00 –32768 8000
H
< –157.00 –32768 8000
H
Underflow

Table of Contents