Digital Modules
3-103
Programmable Logic Controllers S7-300 Module Data
A5E00105505-03
Insulation tested with
Between M
internal
and
supply voltage of the relays
500 VDC
Between M
internal
and
supply voltage of the relays
and the outputs
1500 VAC
Between the outputs of the
different groups
2000 VAC
Current consumption
From the backplane bus
From supply voltage L+
max. 100 mA
max. 160 mA
Power dissipation of the module typ. 3.5 W
Status, Interrupts, Diagnostics
Status display Green LED per channel
Interrupts
Diagnostic interrupt Parameters can be
assigned
Diagnostic functions Parameters can be
assigned
Group error display Red LED (SF)
Diagnostics information
read-out
Possible
Data for Selecting an Actuator
Continuous thermal current max. 5 A
Minimum load voltage / current 10 V /10 mA
1)
Leakage current 11.5 mA
2)
Short-circuit proof according to
IEC 947-5-1
With circuit-breaker of
characteristic B for:
cos 1.0: 600 A
cos 0.5 to 0.7: 900
A
With Diazed 8 A fuse:
1000 A
Switching capacity and lifetime of the contacts
For resistive load
Voltage Current No. of
switching
cyc. (typ.)
24 VDC
24 VDC
24 VDC
230 VAC
230 VAC
230 VAC
5.0 A
2.5 A
1.0 A
5.0 A
2.5 A
1.0 A
0.2 million
0.4 million
0.9 million
0.2 million
0.4 million
0.9 million
Inductive load according to IEC 947-5-1 13 DC/15 AC
Voltage Current No. of
switching
cyc. (typ.)
24 VDC
24 VDC
24 VDC
230 VAC
230 VAC
230 VAC
5.0 A
2.5 A
1.0 A
5.0 A
2.5 A
1.0 A
0.1 million
0.25 million
0.5 million
0.1 million
0.25 million
0.5 million
With a connected RC quenching element (jumper “SJ”
inserted) or with an external protection circuit, you
lengthen the service life of the contacts.
Size of the motor starter max. size 5 to NEMA
Power No. of
switching
cyc. (typ.)
Lamp load (230 VAC) 1000 W
1500 W
25000
10000
Energy-saving
lamps/fluorescent lamps with
electronic ballast
10 58W 25000
Fluorescent lamps,
conventionally compensated
1 58W 25000
Fluorescent lamps,
non-compensated
10 58W 25000
Contact protection RC quenching element
330 , 0.1 F
Connecting two outputs in parallel
For redundant triggering of
a load
Possible (only outputs
with identical load vol-
tage)
To increase performance Not possible
Triggering a digital input Possible
Switch rate
Mechanical max. 10 Hz
For resistive load max. 2 Hz
Inductive loads according
to IEC 947-5-1, DC 13/15
AC
max. 0.5 Hz
For lamp load max. 2 Hz
1)
Without inserted jumper (SJ).
2)
For AC load voltage and inserted jumper (SJ).
Without jumper (SJ) inserted there is a leakage
current
Note