EasyManua.ls Logo

Siemens SIMATIC S7-300 Module data - Page 247

Siemens SIMATIC S7-300 Module data
574 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Analog Modules
4-41
Programmable Logic Controllers S7-300 Module Data
A5E00105505-03
Table 4-41 Parameters of the Analog Input Modules, continued
Parameter ScopePara-
meter
Type
Default
Settings
Value Range
Measurement
Measuring method Deactivated
U Voltage
4DMU Current
(4-wire transmitter)
2DMU Current
(2-wire transmitter)
R-4L Resistance
(four-conductor
connection)
R-3L Resistance
(three-conductor
connection)
RTD-4L Bulb resistor (linear,
four-conductor
connection)
RTD-3L Bulb resistor
(linear, three-conductor
connection)
TC-I
1)
Thermocouple
(internal comparison)
TC-E
1)
Thermocouple
(external comparison)
TC-IL
2)
Thermocouple
(linear, internal
comparison)
TC-EL
2)
Thermocouple
(linear, external
comparison)
TC-L00C
2)
Thermocouple (linear,
reference temp. 0 °C)
TC-L50C
2)
Thermocouple (linear,
reference temp. 50°C)
U
Dynamic
Channel o
r
Channel
group
Measuring range For the settable measuring ranges of
the input channels, please refer to the
individual module description.
"10 V
Reaction with open
thermocouple
Overflow; underflow Overflow
Temperature unit
3)
Degrees Celsius; degrees Fahrenheit;
degrees Kelvin
Degrees
Celsius
Dynamic Module
Module filtering mode 8 channels hardware filter
8 channels software filter
4 channels hardware filter
8
channels,
hardware
filter
Dynamic Module

Table of Contents

Other manuals for Siemens SIMATIC S7-300 Module data

Related product manuals