Product Information on the Manual
A5E00201782-02
Reparameterization steps in RUN mode
Observe the reparameterization steps described in the above manual.
Note the peculiarities of certain modules described in the table.
Example 1:
To change a measuring range for modules, proceed as follows:
1. Change the user program so that the channel to be reparameterized is no
longer evaluated, and download it to the CPU.
2. Change the measuring range for the module in HWCONFIG, and download the
changed configuration to the CPU.
3. Adapt the user program to the changed channel, and download it to the CPU.
Example 2:
When reparameterizing certain modules (see the table), you should ensure that
there is no pending diagnostic event (e.g. a wire break message) before carrying
out reparameterization, since otherwise it may happen in some cases that outgoing
diagnostic events are no longer reported. As a result, the SF LEDs on the CPU,
IM, or module will continue to shine, for example, although the reparameterized
module is working correctly. If such a situation does arise, however, the module
must be removed and then plugged in again.

Table of Contents

Other manuals for Siemens SIMATIC S7-300 Module data

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Siemens SIMATIC S7-300 Module data and is the answer not in the manual?

Siemens SIMATIC S7-300 Module data Specifications

General IconGeneral
SeriesS7-300
ManufacturerSiemens
Protection ClassIP20
SystemSIMATIC S7-300
Digital InputsVaries by module
Digital OutputsVaries by module
Analog InputsVaries by module
Analog OutputsVaries by module
Central Processing UnitVaries by CPU model
Supply Voltage24V DC or 120/230V AC
CPU TypeVaries (e.g., CPU 312, CPU 315, etc.)
MemoryVaries by CPU model
Communication InterfacesMPI, PROFIBUS
Programming LanguagesLAD, FBD, STL, SCL, GRAPH
Operating Temperature0°C to 60°C
Storage Temperature-40°C to 70°C
Relative Humidity10% to 95% (non-condensing)

Related product manuals