4.
Click Submit.
Resetting Reference Priorities to Factory Defaults
To reset all references in the Reference Priority table to their factory default priorities:
1.
Navigate to the Configure Reference Priorities screen via MANAGEMENT > OTHER:
Reference Priority menu.
2.
In the Actions panel, click the Restore Factory Defaults button.
3.3.1.2 The "Local System" Reference
The Local System reference is a "Self" reference, i.e. NetClock uses itself as an input reference
for Time, or as a 1PPS reference. The Local System is a unique input reference in that it can be
used as either the Time reference, or the 1PPS reference, but never both.
Note: For NetClock to operate as a Local System reference, you must have either
a valid external Time reference, or a valid external 1PPS reference.
When the Time reference is configured as Local System, NetClock's System Time is con
sidered a valid reference, as long as the external 1PPS input reference is valid.
166
CHAPTER 3 • NetClock User Reference Guide Rev. 16
3.3 Managing Input References