10 Upgrade Function
10.2Upgrade Procedure
10-3
182582-1CD
182582-1CD
MH900, DX200 Controller
DO NOT turn off the main power supply during automatic
upgrade process.
In case the main power supply is turned off, exercise the
following process.
• Turn on the main power supply of the controller.
– Automatic upgrade might be exercised again.
• In case error occurs during automatic upgrade process.
(1) Prepare CF for upgrading or USB memory.
(2) Press [2], [8] and [HIGH SPEED] at the same time.
-Upgrade of the OS of Programming Pendant
(3) Press [INTERLOCK], [8] and [SELECT] at the same
time.
(4) Exercise manual upgrading.
- Refer to “DX200 Upgrade Procedure”
(165560-1CD).
• If no recovery is made with all the procedure above,
replace the pendant.