4 Connection
4.2 Power Supply
MH900, DX200 Controller
4.2.3 Leakage Breaker Installation
When connecting the leakage breaker to the controller power supply
wiring, use a leakage breaker which can handle high frequencies from the
controller inverter. Leakage breakers which cannot handle high
frequencies may malfunction.
Even with a leakage breaker installed, there is still a possibility of some
high frequency current leakage from the controller inverter. However, this
current leakage presents no safety risks.
Fig. 4-4: Connection of the Leakage Breaker
Table 4-1: Example of High Frequency Leakage Breaker
Maker Model
Mitsubishi Electric Co., Ltd. NV series (manufactured since 1988)
Fuji Electric Co., Ltd. EG, SG Series (manufactured since 1984), or
EW Series.
(1KM)
DX200
Contactor
Noise Filter
T
o control
power supply
unit
Breaker
Leakage
Breaker
Fuse
To converter
3-phase
200/220V AC at 60Hz
or
200V AC 50Hz