4 Connection
4.2 Power Supply
4-5
182582-1CD
182582-1CD
MH900, DX200 Controller
4.2.4 Primary Power Supply Breaker Installation
Install the primary power supply breaker as shown below.
Fig. 4-5: Installation of the Primary Power Supply Breaker
The maximum load value (payload, operation speed, and frequency, etc.)
displays.
However, the power capacity is different depending on work conditions.
Inquire at the nearest branch office listed on the back cover for information
when selecting the transformer.
Table 4-2: Controller Power Capacity, Cable Sizes,
and Breaker Capacities
Manipulator Power
capacity
(kVA)
Cable size
(In case of Cabtyre cable
(three cores)) (mm
2
)
Capacity of
disconnection
Controller (A)
MH900 34 35 100
The power capacity shown above is for a continuous rating
value.
Power capacity is much larger when the robot rapidly
accelerates compared to a continuous rating value.
BreakerBreaker
Controller
for Positioner
Breaker
DX200
Power
Source