EasyManua.ls Logo

YASKAWA V1000 - Page 287

YASKAWA V1000
480 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
n
Unstable Motor Speed when Using PM or IPM
Cause Possible Solutions
The motor code for PM (E5-01) is set incorrectly.
(Yaskawa motors only)
Set parameter E5-01 in accordance with the motor being used.
The drive is operating at less than 10% of the speed
reference.
Consult with Yaskawa about using a different type of motor when attempting to operate at
10% of the speed reference.
Motor hunting occurs.
Set and carefully adjust the following parameters in the order listed:
n8-45 (Speed Feedback Detection Suppression Gain)
n8-55 (Load Inertia for PM Motors)
C4-02 (Torque Compensation Primary Delay Time)
Hunting occurs at start. Increase the S-curve time at the start of acceleration (C2-01).
Too much current is flowing through the drive.
If using a PM motor, set the correct motor code to E5-01.
If using a specialized motor, set parameter E5-xx to the correct value according to the Motor
Test Report.
n
Motor Does Not Operate When the RUN Button on the Digital Operator is Pressed
Cause Possible Solutions
The LOCAL/REMOTE mode is not selected
properly.
Press the LOCAL/REMOTE button to switch. The LO/RE LED should be on for LOCAL
mode.
The drive is not in drive mode. A run command will not be issued. Exit to the drive mode and cycle the run command.
The frequency reference is too low.
If the frequency reference is set below the frequency set in E1-09 (Minimum Output
Frequency), the drive will not operate.
Raise the frequency reference to at least the minimum output frequency.
n
Motor Does Not Operate When an External Run Command is Input
Cause Possible Solutions
The LOCAL/REMOTE mode is not selected
properly.
Press the LOCAL/REMOTE button to switch. The LO/RE LED should be off for REMOTE
mode.
The drive is not in Drive Mode. A run command will not be issued. Exit to the Drive mode and cycle the run command.
The frequency reference is too low.
If the frequency reference is set below the frequency set in E1-09 (Minimum Output
Frequency), the drive will not operate.
Raise the frequency reference to at least the minimum output frequency.
n
Motor Stops During Acceleration or When a Load is Connected
Cause Possible Solution
The load is too heavy.
The limit of motor response may be reached during
rapid acceleration. This may be a result of
improper stall prevention or automatic torque
boost function adjustment.
Increase the acceleration time (C1-01) or reduce the motor load. Also, consider increasing the
motor size and/or drive size.
n
Motor Rotates in One Direction Only
Cause Possible Solutions
"Reverse run prohibited" is selected. If b1-04 (Reverse
Prohibit Operation) is set to 1 (reverse run prohibited),
the drive will not accept a reverse run command.
Set b1-04 = “0” to allow reverse run operation.
The drive prohibits reverse rotation.
Check parameter b1-04.
Set the drive to allow the motor to rotate in reverse (b1-04 = “0”).
A Reverse run signal has not been entered, although
3-Wire sequence is selected.
Make sure that one of the input terminals S3 to S5 used for the 3-Wire sequence has been
set for reverse.
n
Motor Operates at a Higher Speed than the Speed Command
Cause Possible Solution
PID is enabled. If the PID mode is enabled (b5-01 =
1 to 4), the drive output frequency will change to
regulate the process variable to the target setpoint.
The PID can command a speed up to maximum
output frequency (E1-04).
If PID operation is not target, disable PID by setting b5-01 = “0”.
6.9 Troubleshooting without Fault Display
YASKAWA ELECTRIC SIEP C710606 16C YASKAWA AC Drive – V1000 Technical Manual
287
6
Troubleshooting

Table of Contents

Other manuals for YASKAWA V1000

Related product manuals