Register No. Contents
002DH
Output Terminal Status
bit 0 Multi-Function Contact Output (terminal MA/MB-MC)
bit 1 Multi-Function Photocoupler Output 1 (terminal P1 - PC)
bit 2 Multi-Function Photocoupler Output 2 (terminal P2 - PC)
bit 3 to bit F Reserved
002EH Reserved
002FH Frequency Reference Bias (from Up/Down 2 Function), 0.1% units
0030H Reserved
0031H DC Bus Voltage, 1 Vdc units
0032H Torque Monitor, 1% units
0033H Reserved
0034H Product Code 1 [ASCII], Product Type (V0 for V1000)
0035H Product Code 2 [ASCII], Region Code
0036H to 0037H Reserved
0038H PID Feedback, 0.1% units, unsigned, 100% / max. output frequency
0039H PID Input, 0.1% units, signed, 100% / max. output frequency
003AH PID Output, 0.1% units, signed, 100% / max. output frequency
003BH to 003CH Reserved
003DH
Communications Error Log
<3>
bit 0 CRC Error
bit 1 Data Length Error
bit 2 Reserved
bit 3 Parity Error
bit 4 Overrun Error
bit 5 Framing Error
bit 6 Timeout
bit 7 to bit F Reserved
003EH
Output Frequency
r/min
<4>
003FH 0.01% units
0040H to 004AH
Used for various monitors U1-oo. Refer to U: Monitors on page 371 for parameter details.
004BH
Drive status (U1-12)
bit 0 During Run
bit 1 During Zero Speed
bit 2 During Reverse Run
bit 3 During Fault Reset Signal Input
bit 4 During Speed Agree
bit 5 Drive Ready
bit 6 Alarm
bit 7 Fault
bit 8
During Operation Error (oPEoo
bit 9 During Momentary Power Loss
bit A Motor 2 selected
bit B to D Reserved
bit E ComRef status, NetRef status
bit F ComCtrl status, NetCtrl status
004CH to 007EH
Used for various monitors U1-oo,
U4-oo, U5-oo and U6-
oo. Refer to U: Monitors on page 371 for parameter details.
007FH Alarm Code, Refer to Alarm Register Contents on page 427 for alarm codes.
0080H to 0097H
Used for monitors U2-oo, U3-oo. Refer to U: Monitors on page 371 for parameter details and Refer to Fault Trace
Contents on page 426 for register value descriptions.
0098H, 0099H
U4-01 (Cumulative Operation Time)
Example: When U4-01 (Cumulative Operation Time) is 12345 hours, then 0098H = 1234 and 0099H = 5.
009AH, 009BH
U4-03 (Cooling Fan Operation Time)
Example: When U4-03 (Cooling Fan Operation Time) is 12345 hours, then 009AH = 1234 and 009BH = 5.
00ABH
Drive Rated Current
<2>
C.10 MEMOBUS/Modbus Data Table
YASKAWA ELECTRIC SIEP C710606 16C YASKAWA AC Drive – V1000 Technical Manual
421