Drive
Model
Terminal
For Japan and Asia
<1>
For United States
<2>
For Europe and China
<3>
Screw
Size
Tightening
Torque
N•m (lb.in.)
Recomm.
Gauge
mm
2
Wire Range
mm
2
Recomm.
Gauge
AWG, kcmil
Wire Range
AWG, kcmil
Recomm.
Gauge
mm
2
Wire Range
mm
2
2A0020
R/L1, S/L2,
T/L3
5.5 2 to 5.5 10 14 to 10 4 2.5 to 6
M4
1.2 to 1.5
(10.6 to 13.3)
U/T1, V/T2,
W/T3
3.5 2 to 5.5 10 14 to 10 2.5 2.5 to 6
–, +1, +2 5.5 2 to 5.5 14 to 10 2.5 to 6
B1, B2 2 2 to 5.5 14 to 10 2.5 to 6
3.5 2 to 5.5 10 14 to 10 4 2.5 to 6
2A0030
R/L1, S/L2,
T/L3
14 5.5 to 14 8 10 to 6 6 4 to 16
M4
2.1 to 2.3
(18.6 to 20.4)
U/T1, V/T2,
W/T3
8 5.5 to 14 8 10 to 6 6 4 to 16
, 1, 2
14 5.5 to 14 10 to 6 4 to 16
B1, B2 3.5 2 to 5.5 14 to 10 4 to 6
5.5
<4>
5.5 to 14
8
<4>
10 to 6
6
<4>
6 to 16 M5
2 to 2.5
(17.7 to 22.1)
2A0040
R/L1, S/L2,
T/L3
14 5.5 to 14 6 10 to 6 10 6 to 16
M4
2.1 to 2.3
(18.6 to 20.4)
U/T1, V/T2,
W/T3
14 5.5 to 14 8 10 to 6 10 6 to 16
, 1, 2
14 5.5 to 14 10 to 6 6 to 16
B1, B2 5.5 2 to 5.5 14 to 10 4 to 6
14 5.5 to 14 6 10 to 6 10 6 to 16 M5
2 to 2.5
(17.7 to 22.1)
2A0056
R/L1, S/L2,
T/L3
22 14 to 22 4 6 to 4 16 16 to 25
M6
5.4 to 6.0
(47.8 to 53.1)
U/T1, V/T2,
W/T3
14 14 to 22 4 6 to 4 16 16 to 25
, 1, 2
22 14 to 22 6 to 4 16 to 25
B1, B2 14 5.5 to 14 10 to 6 6 to 10 M5
2.7 to 3.0
(23.9 to 26.6)
14 8 to 22 6 8 to 4 16 10 to 25 M6
5.4 to 6.0
(47.8 to 53.1)
2A0069
R/L1, S/L2,
T/L3
30 8 to 38 3 8 to 2 25 10 to 25
M8
9.9 to 11
(87.6 to 97.4)
U/T1, V/T2,
W/T3
22 8 to 38 3 8 to 2 16 10 to 25
, 1, 2
30 8 to 38 8 to 2 10 to 25
B1, B2 14 8 to 14 8 to 6 10 to 16 M5
2.7 to 3.0
(23.9 to 26.6)
14 8 to 22 6 6 to 4 16 10 to 25 M6
5.4 to 6.0
(47.8 to 53.1)
<1> Gauges listed here are for use in Japan and Asia.
<2> Gauges listed here are for use in the United States.
<3> Gauges listed here are for use in Europe and China.
<4> When an EMC filter is
installed, additional measures must be taken to comply with IEC/EN 61800-5-1. Refer to EMC Filter Installation on
page 436 for details.
D.3 UL Standards
YASKAWA ELECTRIC SIEP C710606 16C YASKAWA AC Drive – V1000 Technical Manual
443
D
Standards Compliance

Table of Contents

Other manuals for YASKAWA V1000

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the YASKAWA V1000 and is the answer not in the manual?

YASKAWA V1000 Specifications

General IconGeneral
Input Voltage3-Phase 200-240VAC, 3-Phase 380-480VAC
Output Voltage3-Phase 200-240VAC, 3-Phase 380-480VAC
Output Frequency0-400 Hz
Control MethodV/f control
Overload Capacity150% for 60 seconds
Protection FunctionsOvercurrent, Overvoltage, Undervoltage, Overheating, Short Circuit, Ground Fault
Communication OptionsModbus RTU
Ambient Temperature-10 to +50°C (14 to 122°F)
Storage Temperature-20°C to +65°C (-4°F to 149°F)
Humidity95% (non-condensing)
Cooling MethodForced Air Cooling
EnclosureIP20