<5. Functions>
104
IM 01E21A02-03EN
■Information
Error XD_ERROR BLOCK_ERR
Process
value*
Totalizer Display
No Message STB DTB MTB LTB STB DTB MTB LTB
120 Watchdog -- -- -- -- -- -- -- --
Normal
calculation
Totalizer
processing
continue
Normal
121 Powero󰀨 -- -- -- -- -- -- -- --
Normal
calculation
Totalizer
processing
continue
Normal
122
Instant power
failure
-- -- -- -- -- -- -- --
Normal
calculation
Totalizer
processing
continue
Normal
123
Parameter
backup running
-- -- -- -- -- -- -- --
Normal
calculation
Totalizer
processing
continue
Execute
124
Data logging
running
-- -- -- -- -- -- -- --
Normal
calculation
Totalizer
processing
continue
Icon
133
G/A mismatch
error
17 -- -- -- Other -- -- -- -- -- Alarm
246
Simulation Switch
OFF
-- -- -- -- -- -- -- -- -- -- Normal
248
Simulation Switch
ON
-- -- -- -- -- -- -- -- -- -- Normal
252
Hard Write Lock
SW ON
-- -- -- -- -- -- -- -- -- -- Normal
253 Write Locked -- -- -- -- -- -- -- -- -- -- Normal
254
Hard Write Lock
SW OFF
-- -- -- -- -- -- -- -- -- -- Normal
255 Write Unlocked -- -- -- -- -- -- -- -- -- -- Normal
*Whenadiagnosis-relatedprocess(adhesionresistance,electrodeApotential,electrodeBpotential,
ownoiseandconductivity)isassignedtoAI,avaluemaybeupdatedevenifsetto“HoldPriorsetting”.

Table of Contents