<6. Parameter Lists>
213
IM 01E21A02-03EN
Relative
Index
Index
Parameter
Name
Default Value
Write
Mode
Description
AI1 AI2 AI3
AI4
(only
AXG)
29 4029 4129 4229 4329 LO_PRI 0 AUTO
SpeciesthepriorityfortheLO
alarm. Meanwhile, to activate
an alarm on communication,
it is necessary to specify the
priority for alarm activation in
advance. To activate an alarm,
set 3 or more. By sending with
priority information being added
in a communication frame
when the alarm is activated, for
example, the alarm is used to
applyaltertoignorevalues
belowthespeciedpriorityon
the host side.
30 4030 4130 4230 4330 LO_LIM -FLT_MAX AUTO
Speciesalimitvalueforthe
LO alarm.
31 4031 4131 4231 4331 LO_LO_PRI 0 AUTO
Speciesthepriorityofthe
LO_LO alarm. Meanwhile,
to activate an alarm on
communication, it is necessary
to specify the priority for
alarm activation in advance.
To activate an alarm, set 3 or
more. By sending with priority
information being added in a
communication frame when the
alarm is activated, for example,
the alarm is used to apply a
ltertoignorevaluesbelowthe
speciedpriorityonthehost
side.
32 4032 4132 4232 4332 LO_LO_LIM -FLT_MAX AUTO
Speciesalimitvalueforthe
LO_LO alarm.
33 4033 4133 4233 4333 HI_HI_ALM
0(Uninitialized)
0(Uninitialized)
0,0
0(Other)
0.0
AUTO
-
-
-
-
Indicates information about the
HI_HI alarm that occurred.
34 4034 4134 4234 4334 HI_ALM
0(Uninitialized)
0(Uninitialized)
0,0
0(Other)
0.0
AUTO
-
-
-
-
Indicates information about the
HI alarm that occurred.
35 4035 4135 4235 4335 LO_ALM
0(Uninitialized)
0(Uninitialized)
0,0
0(Other)
0.0
AUTO
-
-
-
-
Indicates information about the
LO alarm that occurred.
36 4036 4136 4236 4336 LO_LO_ALM
0(Uninitialized)
0(Uninitialized)
0,0
0(Other)
0.0
AUTO
-
-
-
-
Indicates information about the
LO_LO alarm that occurred.
37 4037 4137 4237 4337
BLOCK_ERR_
DESC_1
0x00000000 -
Bit assignment complies with
the Communication standard
specications.