4-10
IM MW100-01E
The MW100 can be detected using the Search button, but browser connection fails.
Possible Problem Corrective Action Ref. section
The IP address is set to the default value. Enter the correct IP address. *
The default value cannot be used to make the
connection.
There is a problem in the network confi guration. Check that the IP address, subnet mask, and default *
gateway settings on the MW100 are correct.
* See the MW100 Viewer Software User’s Manual.
The Calibrator cannot connect to the MW100.
Possible Problem Corrective Action Ref. section
Attempting to make multiple connections. Exit all other software programs. 4.3,*
* See the MW100 Viewer Software User’s Manual.
The connected input/output module is not detected.
Possible Problem Corrective Action Ref. section
Module connection or module startup error. Turn OFF the power. Detach the input/output module 2.5
Attached the module while the power was ON. once and attach it again.
Carried out an incorrect calibration. Recalibrate. 4.3,*
* See the MW100 Viewer Software User’s Manual.
4.3 Troubleshooting