2-19
IM MW100-01E
Installation and Wiring
2
Wiring with the Digital Output Module
C
NO
250 VDC/0.1 A, 250 VAC/2 A, or
30 VDC/2 A (resistance load)
Main Output Specifications
Contact mode: A contact (SPST)
Contact capacity: 250 VDC/0.1 A, 250 VAC/2 A, or 30 VDC/2 A (resistance load)
Terminal type: Clamp, attached and removed in units of 5 channels
Applicable wire size: 0.08 to 2.5 mm
2
(AWG28 to 12)
Note
Do not connect anything to the empty terminals of the digital output module.