2-13
IM MW100-01E
Installation and Wiring
2
2.4 Connecting Signal Wires
Wiring the 4-Wire RTD Resistance Input Module
Votage
Nothing connected to
the I or C terminal
Resistance, RTD
+
Resistance per lead wire of 10 Ω or less
DC voltage
Input
Contact
• DC voltage input/DI (contact) input • RTD input, resistance input
• DC current input
DC current input
Shunt resistor
Example: For 4 to 20 mA input, shut resistance values
should be 250 Ω±0.1%.
+
C
A
B
I
C
A
B
I
C
A
B
I
Terminal type: Clamp
Applicable wire size: 0.14 to 1.5 mm
2
(AWG26 to 16)
Wiring the Strain Input Module
1 Gauge Method
Jumper setting switch
ON
OFF
No.1
No.2
No.3
No.4
No.5
A(+V)
B( L)
C(-V)
D( H)
-B12, -B35
E
e
Rg
R
R
R
Rg
No.1
ON
No.2
ON
No.3
ON
No.4
OFF
No.5
OFF
Rg
R: fixed resistance
r: resistance value of lead
wire
Rg: resistance value of strain
gauge
e: output voltage from bridge
E: voltage applied to bridge
Bridge head
switch
-NDI
Rg
ON
1 2 3 4 5
1
2
3
4
5
6
7
8
OFF
SW
Bridge head
(701955 or 701956)
SW1
ON
SW2
ON
SW3
ON
SW4
ON
SW5
OFF

Table of Contents