App-11
IM MW100-01E
Appendix
App
Appendix 4 E-Mail Format
In the explanations that follow,
CRLF
means “carriage return/line feed.”
A user-defined character string can be attached to the subject of each mail.
Alarm Notification E-mail Format
• Subject
Subject: [Alarm Summary]
• Syntax
CRLF
Alarm_SummaryCRLF
DATE_yy/mo/ddCRLF
TIME_hh:mi:ssCRLF
CRLF
<Alarm Summary>CRLF
cc____lq_aaaCRLF
····························
mmmm_lq_aaaCRLF
···························
CRLF
s_cc_uuuuuufdddddEfpCRLF
···························
s_mmmm_feeeeeeeeEfpCRLF
···························
CRLF
yy
Year (
00
to
99
)
mo
Month (
01
to
12
)
dd
Day (
01
to
31
)
hh
Hour (
00
to
23
)
mi
Minute (
00
to
59
)
ss
Seconds (
00
to
59
)
cc
Measurement ch no. (
01
to
60
, SKIP channels not output)
mmmm
Alarm level (
1
to
4
)
q
Alarm type (
H
,
L
,
h
,
l
,
R
,
r,
T,
t
)
H
(upper limit alarm),
L
(lower limit alarm),
h
(differential upper limit
alarm),
l
(differential lower limit alarm),
R
(high limit on rate of
change alarm),
r
(low limit on rate of change alarm),
T
(delay high limit
alarm),
t
(delay low limit alarm)
aaa
Alarm status (
off
,
on
)
s
Data status (
N
,
D
,
O
,
E
)
N
(normal),
D
(differential input),
O
(over),
E
(error)
uuuuuu
Unit information (output using 6 chars., left justified)
mV____
: mV
V_____
: V
^C____
: °C
XXXXXX
: (user specified char. string)