IM MW100-01E
Initializing Settings
Two types of settings initialization are available.
Initialization of all settings:
Initializes all setting values and measured values on the main unit.
You can perform initialization through communication commands
or by resetting the dip switch positions and turning ON the unit.
When initialized using communication commands, module
recognition information is not initialized.
Initialization of all settings excluding communication parameters:
All settings and measured values except for communication
parameters and module recognition information are initialized.
Executed using communication commands.
Initialization of the CF Card
Formats the CF card.
Format type: Supports FAT12/FAT16, logical format only
CF card size: 2 GB maximum
File name format: 8.3 format
General Specifications
Operating temperature: –20 to 60°C
Operating humidity: 20 to 80% RH for –20 to 40 °C
10 to 50% RH for 40 to 50 °C
5 to 30% RH for 50 to 60 °C
Power consumption: Approx. 8 W
Insulation resistance: Between power supply terminal and earth terminal: 20 MΩ or
more (500 VDC)
Withstand Voltage AC power Between AC power supply terminal and earth
terminal: 1500 VAC (50/60 Hz) for one minute
DC power Between DC power supply terminal and earth
terminal: 1000 VAC (50/60 Hz) for one minute
External dimensions: Approx. 105 (W) × 131 (H) × 137 (D) mm
Weight: Approx. 1kg.
5.2 Main Module Specifications