Specification
5
5.5 10-CH, Medium-Speed Universal Input Module
Specifications
Style number: S1
Type of measurement: DC voltage, thermocouple, 3-wire RTD, DI (contact, LEVEL)
Number of inputs: 10
Input method: Floating unbalanced input, insulation between channels (b
terminal common for RTD)
A/D resolution: 16 bits (±20000/±6000/0 to 60000)
Measurement range and accuracy:
The accuracy applies to standard operating conditions:
Ambient temp: 23±2°C, ambient humidity: 55±10% RH, supply
voltage: 90 to 250 VAC, power frequency: 50/60 Hz ± 1%, warm-
up time: at least 30 minutes, without adverse conditions such as
vibrations.
Input
DC voltage
20 mV
60 mV
200 mV
2 V
6 V
20 V
100 V
60mV (high res.)
1V
6V (high res.)
R
1
S
1
B
1
K
1
E
1
J
1
T
1
L
2
U
N
3
W
4
KPvsAu7Fe
PR40-20
NiNiMo
WRe3-25
W/WRe26
Type-N(AWG14)
TXK GOST
–20.000 to 20.000 mV
–60.00 to 60.00 mV
–200.00 to 200.00 mV
–2.0000 to 2.0000 V
–6.000 to 6.000 V
–20.000 to 20.000 V
–100.00 to 100.00 V
0.000 to 60.000 mV
–1.0000 to 1.0000 V
0.0000 to 6.0000 V
0.0 to 1760.0°C
0.0 to 1820.0°C
–200.0 to 1370.0°C
–200.0 to 800.0°C
–200.0 to 1100.0°C
–200.0 to 400.0°C
–200.0 to 900.0°C
–200.0 to 400.0°C
0.0 to 1300.0°C
0.0 to 2315.0°C
0.0 to 300.0K
0.0 to 1900.0°C
0.0 to1310.0°C
0.0 to 2400.0°C
0.0 to 2400.0°C
0.0 to 1300.0°C
–200.0 to 600.0°C
Measurement Accuracy
Integration Time: 16.67 ms
or More
Highest
Resolution
(1 digit)
(0.05% of rdg + 5 digits)
(0.05% of rdg + 2 digits)
(0.05% of rdg + 2 digits)
(0.05% of rdg + 5 digits)
(0.05% of rdg + 2 digits)
(0.05% of rdg + 2 digits)
(0.05% of rdg + 2 digits)
(0.05% of rdg + 20 digits)
(0.05% of rdg + 2 digits)
(0.05% of rdg + 20 digits)
(0.05% of rdg + 1°C)
Except 0 to 100°C: 3.7°C, 100 to
300°C: 1.5°C for R and S;
400 to 600°C: 2°C, less than
400°C: not guaranteed for B
(0.05% of rdg + 0.7°C)
Except –200°C to –100°C:
(0.05% of rdg + 1°C)
(0.05% of rdg + 0.5°C)
Except –200°C to –100°C:
(0.05% of rdg + 0.7°C) for J and L
(0.05% of rdg + 0.7°C)
(0.05% of rdg + 1°C)
(0.05% of rdg + 0.7K)
(0.05% of rdg + 2.5°C)
Except 300 to 700°C: 6°C,
less than 300°C: not guaranteed
(0.05% of rdg + 0.7°C)
(0.05% of rdg + 2°C)
Except 0 to 200°C: 2.5°C,
more than 2000°C:
(0.05% of rdg + 4°C)
(0.05% of rdg + 2°C)
Except 100 to 300°C: 4°C,
less than 100°C: not guaranteed
(0.05% of rdg + 0.7°C)
(0.05% of rdg + 0.5°C)
Except –200 to 0°C:
(0.2% of rdg + 0.7°C)
Rated
Measurement
Range
1 V
10 V
10 V
100 V
1 mV
1 mV
10 mV
1V
100V
100V
0.1°C
0.1K
0.1°C
1 R, S, B, K, E, J, T: ANSI, IEC 584, DIN IEC 584, JIS C 1602-1995
2 L: Fe-CuNi, DIN43710/U: Cu-CuNi, DIN 43710
3 N: Nicrosil-Nisil, IEC 584, DIN IEC 584
4 W: W•5%RE-W•26%Re (Hoskins Mfg Co)
Thermocouple
(excludes RJC accuracy)
Measurement Accuracy
Integration Time: 16.67 ms
(0.1% of rdg + 25digits)
(0.1% of rdg + 10digits)
(0.1% of rdg + 100 digits)
(0.1% of rdg + 10 digits)
(0.1% of rdg + 100 digits)
(0.1% of rdg + 4°C)
Except 0 to 100°C: 10°C, 100 to
300°C: 5°C for R and S;
400 to 600°C: 7°C, less than
400°C: not guaranteed for B
(0.1% of rdg + 3.5°C)
Except –200°C to –100°C:
(0.1% of rdg + 6°C)
(0.1% of rdg + 2.5°C)
Except –200°C to –100°C:
(0.1% of rdg + 5°C) for J and L
(0.1% of rdg + 3.5°C)
(0.1% of rdg + 7°C)
(0.1% of rdg + 3.5K)
(0.1% of rdg + 12°C)
Except 300 to 700°C: 25°C,
less than 300°C: not guaranteed
(0.1% of rdg + 2.7°C)
(0.1% of rdg + 7°C)
Except 0 to 200°C: 12°C,
more than 2000°C:
(0.1% of rdg + 11°C)
(0.1% of rdg + 8.5°C)
Except 100 to 300°C: 12°C,
less than 100°C: not guaranteed
(0.1% of rdg + 3.5°C)
(0.1% of rdg + 2.5°C)
Except –200 to 0°C:
(1% of rdg + 2.5°C)
Measurement
Range
Type