2-18
IM MW100-01E
Wiring with the Analog Output Module
External power supply Voltage
V+
Load
+
24 V
power supply
(when using current output)
Direction of
current
Vext
Current
I+
Load
CAUTION
Two power supply terminals are connected internally. Therefore, do not connect
a separate external power supply to them. Fire can result.
Main Output Specifications
Terminal type: Clamp, attached and removed in units of 4 channels
Load impedance: Voltage 5 kΩ or more
Current 600 Ω or less.
Applicable wire size: 0.08 to 2.5 mm
2
(AWG28 to 12)
Wiring with the PWM Output Module
External power supply Pulse width output
V+
Load
+
4 to 28 V
power supply
CAUTION
Two power supply terminals are connected internally. Therefore, do not connect
a separate external power supply to them. Fire can result.
Main Output Specifications
Output capacity: 1A/ch max, however, 4 A or less total for all modules
*, **
Terminal type: Clamp, attached and removed in units of 4 channels
Applicable wire size: 0.08 to 2.5 mm
2
(AWG28 to 12)
*
A 1A current limit circuit is built in to the output circuit. Once the current limit circuit is ON,
the circuit continues to operate unless the external power supply is turned OFF.
**
This module has a built-in fuse. The built-in fuse protects against fires or abnormal
emissions of heat due to load shortages or other abnormalities. It does not protect against
damage to internal circuits.
2.4 Connecting Signal Wires