Wiring with the Analog Output Module
External power supply Voltage
V+
Load
+
24 V
power supply
(when using current output)
Direction of
current
Vext
Current
I+
Load
CAUTION
Two power supply terminals are connected internally. Therefore, do not connect
a separate external power supply to them. Fire can result.
Main Output Specifications
Terminal type: Clamp, attached and removed in units of 4 channels
Load impedance: Voltage 5 k or more
Current 600 or less.
Applicable wire size: 0.08 to 2.5 mm
2
(AWG28 to 12)
Wiring with the PWM Output Module
External power supply Pulse width output
V+
Load
+
4 to 28 V
power supply
CAUTION
Two power supply terminals are connected internally. Therefore, do not connect
a separate external power supply to them. Fire can result.
Main Output Specifications
Output capacity: 1A/ch max, however, 4 A or less total for all modules
*, **
Terminal type: Clamp, attached and removed in units of 4 channels
Applicable wire size: 0.08 to 2.5 mm
2
(AWG28 to 12)
*
A 1A current limit circuit is built in to the output circuit. Once the current limit circuit is ON,
the circuit continues to operate unless the external power supply is turned OFF.
**
This module has a built-in fuse. The built-in fuse protects against fires or abnormal
emissions of heat due to load shortages or other abnormalities. It does not protect against
damage to internal circuits.
2.4 Connecting Signal Wires

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the YOKOGAWA MW100 and is the answer not in the manual?

YOKOGAWA MW100 Specifications

General IconGeneral
BrandYOKOGAWA
ModelMW100
CategoryData Loggers
LanguageEnglish

Related product manuals