3-12
IM MW100-01E
Login Function and User Settings
Using this function, you can restrict access to previously registered users.
1.
From the Top screen, click Communication Setting > User Setting.
Login Function
2.
Select the Enable check box. This enables the login function.
User Settings
3.
Select Admin or User in the Level list under User List. Only Admin can be
selected for list number 01.
4.
Enter the user name to set in the User Name box under User List.
5.
After selecting the Password check box under User List, enter the password to
be assigned to the user in the Password box. If you do not select the check box,
you cannot enter the password.
6.
Click the Apply button. The setting changes take effect.
Note
If you forget the password for the user set to the Admin level, there is no way to recover except
initializing the MW100 using dip switch 1. Be sure not to forget the password.
For the initialization procedure using the dip switch, see section 4.6, “System Initialization.”
3.2 Connection to the MW100