1-42
IM MW100-01E
1.9 Functions of the 8-CH, Medium-Speed Analog
Output Module
The module has eight outputs for voltage or current.
An external power source (24 V) is required for current output.
For voltage output only, an external power source is not required.
Input terminal (clamp terminal)
Terminal cover
Output Types
Output Type Notation
No output SKIP
Analog output AO
Output Method
Output Method Notation Actions
Transmission output Trans Outputs a voltage or current according to the
measured results of the input channel specified on
the same unit. You can also produce pattern output
using the broken line input function.
Arbitrary output Comm.Input Outputs specified values based on values sent from
the PC.
Output Range
Output Range Notation Output range
Voltage 10 V –10.000 V to 10.000 V
Current 20 mA 0.000 mA to 20.000 mA
Output Update Interval
The output is updated at 100-ms (minimum) intervals. It is not synchronized to the
measurement interval.
Operation upon Startup and Errors
See section 1.11, “Operation of the Eight-Channel Medium-Speed Analog Output Module
and the Eight-Channel Medium Speed PWM Output Module.”
Output Operation during Calibration
Calibration Condition Output Operation
Channels being calibrated Arbitrary output (output of calibration value)
Non-calibrated channels Holds the output value (holds the value last output during steady
operation (see section 1.11))