2-10
IM MW100-01E
2.4 Connecting Signal Wires
CAUTION
If a large pulling force is applied to the input/output signal wires connected to the
MW100, the terminal or signal wire may break. To prevent this from happening,
secure all the wiring cables to the installation panel.
Wiring of the Strain Input Module (-NDI)
When connecting a bridge head, in order that the empty weight of the cable
does not exceed 5 kg, ensure that the cable does not hang down more than 1.5
m (the distance to the floor). If the cable hangs longer than 1.5 m, secure the
cable to the installation panel or some other location.
Do not apply a voltage exceeding the value indicated below to the input
terminals of the universal input modules. Doing so can damage the modules.
Maximum input voltage
Voltage range less than or equal to 1 VDC, TC, RTD, and DI: ±10 VDC
Other voltage ranges: ±120 VDC
Maximum common mode voltage: 600 VACrms (50 / 60 Hz)
Do not apply a voltage exceeding the value indicated below to the input
terminals of the 10-CH High-Speed Digital Input Module and the output terminals
of the 10-CH Medium-Speed Digital Output Module. Doing so can damage the
modules.
Maximum input voltage
10-CH, High-Speed Digital Input module: ±10 VDC (-D05), ±50 VDC (-D24)
10-CH, Medium-Speed Digital Output module: 250 VAC or 250 VDC
Maximum common mode voltage: 250 VACrms (50/60 Hz)
Do not apply a voltage exceeding the value indicated below to the input
terminals of the 4-Wire RTD resistance input module. Doing so can damage the
modules.
Maximum input voltage
Voltage range less than or equal to 1 VDC, RTD, resistance, and DI (contact):
±10 VDC
Other measurement ranges: ±120 VDC
Maximum common mode voltage: 600 VACrms (50/60 Hz)
Do not apply a voltage exceeding the value indicated below to the input
terminals of the strain input modules. Doing so can damage the modules.
Maximum input voltage: ±10 VDC (between H-L) continuous
Maximum common-mode voltage
Between input and ground: 250 VACrms (-B12, -B35), 30 VACrms (-NDI)
Do not apply a voltage exceeding the value indicated below to the input
terminals of the analog output modules or the PWM output modules. Doing so
can damage the modules.
Maximum common-mode voltage
Between output terminals and earth terminal: 250 VACrms (50/60 Hz)
This is a measurement category II (IEC61010-1) and overvoltage category II
(CSA1N.61010-1) instrument.

Table of Contents