Operating Modes
Parameter manual b maXX BM5800
Document No.: 5.16029.03 Baumüller Nürnberg GmbH
614
of 814
3.8
– The speed actual value of the slave axis, under consideration of the inverse trans-
mission factor, corresponds with the start speed for the ramp generator. This en-
ables the activation of a moved slave axis on the fly.
– Synchronicity is considered to be established when the slave axis enters the
Z145.6– Synchronization velocity window for the first time around the speed set val-
ue of the master axis. From this point, the controller will independently switch from
the internal ramp generator to the set value of the master axis.
– If the master axis changes its speed during synchronization in progress, the target
speed for the ramp generator will be adjusted accordingly.
If the new target speed slows down, braking occurs with a deceleration value Z145.8–
to the new value.
In the case of the S-curve, the current acceleration value must first be reduced through
the jerk value setting
Z145.9–, which means the speed will first be increased further.
Procedure with Stop through the control word and subsequent synchronization after
canceling the Stop:
– The Stop command is requested through the Z108.1– Control word bit 8 = 1.
– Automatic activation of the internal ramp generator using Parameters Z145.7– to
Z145.9–. Disconnect the slave axis from the main axis set value.
– The target speed for the ramp generator is set to 0.
– The speed actual value of the slave axis, under consideration of the inverse trans-
mission factor, corresponds with the start speed for the ramp generator.
– The Stop cannot be ended until the speed set value at the output of the ramp gen-
erator has reached 0.
– The stop is canceled by deleting the control word bit 8.
– After canceling the Stop, the target speed of the ramp generator is set to the current
speed set value of the master axis.
– Synchronicity is considered to be established when the slave axis enters the
Z145.6– Synchronization velocity window for the first time around the speed set val-
ue of the master axis. From this point, the controller will independently switch from
the internal ramp generator to the set value of the master axis.
– If the master axis changes its speed during synchronization in progress, the target
speed for the ramp generator will be adjusted accordingly.
If the new target speed slows down, braking occurs with a deceleration value Z145.8–
to the new value.
In the case of the S-curve, the current acceleration value must first be reduced through
the jerk value setting
Z145.9–, which means the speed will first be increased further.
NOTE!
With deactivated speed synchronization (bit 8 = 0) the slave axis may not be added
to a moving master axis and a stop may not be ended. Because the master axis set
value is transferred immediately, an undesired fast acceleration may occur depend
-
ing on the master speed. This may lead to damage to the mechanism and trigger a
error when position error monitoring is active.