Description of the Software Modules and Parameters
Parameter manual b maXX BM5800
Document No.: 5.16029.03
97
of 814
3
107.5 Nominal operation mode
At Baumüller, the operating mode of the motor is specified in the form Sx-yy%.
The high byte of the mode is designated by the number in front of the dash, the low byte
encodes the percentage value.
Using the example of S3-40%:
High byte = 3 decimal,
Low byte = 40 decimal.
107.6 Nominal power
Nominal output of the motor (at nominal temperature, motor warm). The value displayed
is read from motors with an electronic identification plate and is used to calculate the nom
-
inal torque (Z107.43).
107.7 Nominal speed
Nominal speed of the motor.
If the motor has no electronic identification plate, the nominal speed must be entered.
107.8 Nominal voltage
Nominal voltage of the motor. The value displayed is read from motors with an electronic
identification plate and is used for motor control at the sensorless asynchronous motor.
107.9 Nominal current
Nominal current of the motor; required for I
2
t monitoring and for controlling asynchronous
motors. If the motor has no electronic identification plate, the nominal current must be en
-
tered.
107.10 Standstill current
Display of the motor standstill current.
The value displayed is read from motors with an electronic identification plate.
The parameter can be changed in the inhibited state, only.