SUMMARY STEPS
1.
Use the wire stripper to strip one end of the AWG #6 wire approximately 0.75 inches (1.905 cm).
2.
Insert the AWG #6 wire into the wire receptacle in the grounding lug. Use the manufacturer's recommended
crimping tool to carefully crimp the wire receptacle around the wire. This step is required to ensure proper
mechanical connection.
3.
Attach the grounding lug to the wire on the left to avoid having the grounding wire overlapping the power
supply.
4.
Locate the chassis ground connector on the side of your chassis.
5.
The following image shows how to attach the grounding lug to the chassis ground connector.
6.
Insert the two screws through the holes in the grounding lug.
7.
Use the Number 2 Phillips screwdriver to carefully tighten the screws until the grounding lug is held firmly
to the chassis. Do not overtighten the screws.
8.
Connect the opposite end of the grounding wire to the appropriate grounding point at your site to ensure
an adequate chassis ground.
DETAILED STEPS
Step 1
Use the wire stripper to strip one end of the AWG #6 wire approximately 0.75 inches (1.905 cm).
Step 2
Insert the AWG #6 wire into the wire receptacle in the grounding lug. Use the manufacturer's recommended crimping
tool to carefully crimp the wire receptacle around the wire. This step is required to ensure proper mechanical connection.
The following image shows the parts of the grounding lug.
Figure 160: Parts of the Grounding Lug
Ground lug screws3Chassis ground connector
holes
1
Ground wire4Grounding lug2
Cisco ASR 1000 Series Router Hardware Installation Guide
348
Cisco ASR 1002-X Router Overview and Installation
Attaching a Chassis Ground Connection

Table of Contents

Other manuals for Cisco ASR 1002-X

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Cisco ASR 1002-X and is the answer not in the manual?

Cisco ASR 1002-X Specifications

General IconGeneral
Form FactorRack-mountable
Rack Units2RU
Integrated ServicesYes
Maximum Memory16 GB
Built-in Gigabit Ethernet Ports6
Input Voltage100-240 VAC
Operating Temperature32 to 104°F (0 to 40°C)
RedundancyPower supply redundancy
Network Interface ModulesUp to 4 SPA/SIP slots
Embedded Services Processor (ESP)ESP-20
Maximum Packet per Second (PPS)15 Mpps
Height3.5 inches
Fixed Ports6 GE ports
Memory4 GB (default), 16 GB (maximum)
Power SupplyDual power supplies (AC or DC)
Dimensions (H x W x D)3.5 x 17.5 x 19.0 in (8.9 x 44.5 x 48.3 cm)