EasyManua.ls Logo

Hioki PQ3100 - Measurement Items List

Hioki PQ3100
242 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
156
Input Specications/Output Specications/Measurement Specications
2. Measurement items
(1) Item detected at a sampling frequency of 200 kHz with no gaps
Notation 1P2W 1P3W 1P3W1U 3P3W2M 3P3W3M 3P4W
Transient overvoltage Tran 1, 4 1, 2, 4 1, 4 1, 2, 4 1, 2, 3 1, 2, 3, 4
(2) Items measured each 1 cycle with no gaps
Notation 1P2W 1P3W 1P3W1U 3P3W2M 3P3W3M 3P4W
Frequency (1 wave) Freq_wav U1
(3) Item measured over 1 cycle with no gaps, commencing at a fundamental zero crossing, and
refreshed each half-cycle
Notation 1P2W 1P3W 1P3W1U 3P3W2M 3P3W3M 3P4W
RMS voltage refreshed
each half-cycle
Urms1/2 1, 4 1, 2, 4 1, 4 1, 2, 3, 4 12, 23, 31 1, 2, 3, 4
Swell Swell 1 1, 2 1 1, 2, 3 12, 23, 31 1, 2, 3
Dip Dip 1 1, 2 1 1, 2, 3 12, 23, 31 1, 2, 3
Interruption Intrpt 1 1, 2 1 1, 2, 3 12, 23, 31 1, 2, 3
RMS current refreshed
each half-cycle
Irms1/2 1, 4 1, 2, 4 1, 2, 3, 4
(4) Items measured over half-cycle with no gaps
Notation 1P2W 1P3W 1P3W1U 3P3W2M 3P3W3M 3P4W
Inrush current Inrush 1, 4 1, 2, 4 1, 2, 3, 4
(5) Items measured over the approximately 200-ms (10/12-cycle for 50 Hz / 60 Hz, respectively)
aggregation with no gaps
Notation 1P2W 1P3W 1P3W1U 3P3W2M 3P3W3M 3P4W
Frequency (200 ms) Freq U1
Frequency (10 sec) Freq10s U1
Voltage waveform peak Upk+, Upk− 1, 4 1, 2, 4 1, 4 1, 2, 3, 4 12, 23, 31 1, 2, 3, 4
Current waveform peak Ipk+, Ipk− 1, 4 1, 2, 4 1, 2, 3, 4
RMS voltage (phase)
Urms 1, 4
1, 2, AVG,
4
1, 4
1, 2, 3,
AVG
1, 2, 3,
AVG, 4
RMS voltage (line)
1, 2, 3,
AVG, 4
12, 23,
31, AVG
12, 23,
31, AVG,
4
Voltage DC Udc 1, 4 1, 2, 4 1, 4 1, 2, 3, 4 12, 23, 31 1, 2, 3, 4
Voltage CF Ucf 1, 4 1, 2, 4 1, 4 1, 2, 3, 4 12, 23, 31 1, 2, 3, 4
RMS current Irms 1, 4 1, 2, AVG, 4 1, 2, 3, AVG, 4
Current DC Idc 1, 4 1, 2, 4 1, 2, 3, 4
Current CF Icf 1, 4 1, 2, 4 1, 2, 3, 4
Active power P 1 1, 2, SUM 1, 2, 3, SUM
Active energy WP+, WP− 1 SUM

Table of Contents

Other manuals for Hioki PQ3100

Related product manuals