167
Input Specications/Output Specications/Measurement Specications
29. Harmonic power measurement specications Pharm
Measurement method Indicates harmonic power for each channel and the sum for multiple channels
(For details, see Calculation Formula.)
Analysis window width 10 cycles/12 cycles
Window point count Rectangular 2,048 points
Displayed items From 0th to 50th order
Options for RMS and content percentage
For content percentage, when the RMS is 0, all orders should be set to 0%.
Measurement range Depends on the voltage × current range combination (see Power range conguration
table)
Measurement accuracy 0th order : ±0.5% rdg. ±0.5% f.s. + (current sensor accuracy)
1st to 20th order: ±0.5% rdg.±0.2% f.s. + (current sensor accuracy)
21st to 30th order: ±1.0% rdg.±0.3% f.s. + (current sensor accuracy)
31st to 40th order: ±2.0% rdg.±0.3% f.s. + (current sensor accuracy)
41st to 50th order: ±3.0% rdg.±0.3% f.s. + (current sensor accuracy)
(Note: While using 2000 A range of Model CT7742, f.s. tolerance should be 2.5 times
the value)
30. Interharmonic voltage and interharmonic current measurement specications
Uiharm, Iiharm
Measurement method Following the harmonic analysis, indicated added the harmonics components between
the integer orders harmonics components.
Analysis window width 10 cycles/12 cycles
Window point count Rectangular 2,048 points
Displayed items From order 0.5 to 49.5
Options for RMS and content percentage
For content percentage, when the RMS is 0, all orders should be set to 0%.
Measurement range Interharmonic voltage: 1000.0 V
Interharmonic current: Depends on the current sensor in use
Measurement accuracy Interharmonic voltage:
Harmonic input has been specied with the declared input voltage, 100 V to 440 V,
input.
With a harmonic input of 1% or more of the declared input voltage input: ±10.0% rdg.
With a harmonic input of less than 1% of the declared input voltage: ±0.05% of the
declared input voltage
Interharmonic current: Accuracy not dened
31. Harmonic voltage phase angle and harmonic current phase angle measurement
specications Uphase, Iphase
Measurement method Applies IEC61000-4-7 Ed2.1: 2009.
Analysis window width 10 cycles/12 cycles
Window point count Rectangular 2,048 points
Displayed items Indicates the harmonic phase angle component of the integer-numbered order
(including the fundamental wave component)
(Where the wave phase angle is 0°.)
Measurement range 0.00° to ±180.00°
Measurement accuracy Accuracy not dened
14
Specications