171
QUICK SET Specications
Easy settings course
Course
Setting items
Voltage events Inrush current Trend record only EN50160
Wiring Set in advance
Current sensor Set in advance
Current range
Set in advance
Switches to an
upper range when
the reference value
is 1/5th or more of
the rated range
Set in advance
Measurement frequency Set in advance
Declared input voltage Set in advance
Selection of
calculation
method
Urms type Default
THD type THD_F
PF/Q/S
calculation
selection
RMS value calculation
Recorded item settings Yes harmonic
Recording interval 1 min 10 min
Event hysteresis 1% 2%
Transient overvoltage 70% of the
declared input
voltage
Off
100% of the
declared input
voltage
Voltage Swell 110% of the
declared input
voltage
Off
110% of the
declared input
voltage
Voltage Dip 90% of the
declared input
voltage
Off
90% of the
declared input
voltage
Interruption 10% of the
declared input
voltage
Off
5% of the declared
input voltage
Frequency (200 ms) Nominal input
frequency ±5 Hz
Off
Nominal input
frequency ±0.5 Hz
Frequency (1 wave) Off Off
Inrush current
Off
200% of the
reference value
Off
Voltage total harmonic
distortion
5% Off 8%
Current total harmonic
distortion
Off Off
• Range settings for inrush current should not be changed without considering the reference value when the prior set
range is at its maximum. A value of 10% of the range is used as threshold value when the reference value (measured
value at the effective time of the easy setting) is 10% or less of the range.
If the reference value of 200% exceeds the rated range, the rated range value is set as the threshold value.
• Voltage THD is set as off if the RMS voltage value is 3% f.s. or less of the range.
• After easy setting, (not only for easy setting) if the VT, CT are changed after setting the threshold value, the
threshold value does not change. (Event threshold value is set again after setting the VT, CT)
• Fundamentally, the settings that are not included in the table are taken as default values.
14