EasyManuals Logo

Honeywell DR4500A User Manual

Honeywell DR4500A
266 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #231 background imageLoading...
Page #231 background image
Troubleshooting / Service
Troubleshooting Procedures
Release M DR4500A Classic Series Circular Chart Recorder With or Without Control Product Manual 217
April 2017
Table 9-14 Procedure #9—Troubleshooting relay output failure symptoms
Step
What to do
How to do it or where to find the data
1
Be sure the recorder is configured for
relay output.
Refer to Section 3 - Configuration. Make sure
OUT ALG selection = TIME.
2
Be sure all the recorder and control
related data is correct.
Refer to Section 3 - Configuration .
Check the Tuning, Algorithm, and Control data.
3
Check that the applicable output relay
actuates properly. If it does, go to step 4.
Put the recorder into manual mode and adjust the
output manually to raise or lower the PV around
the setpoint. Listen for the click of the relay as the
PV moves in either direction. Observe OUT 1 or 2
indicator on the front display.
4
Check the control relay jumper positions.
Refer to Section 3 - Configuration.
5
Check the field wiring.
Refer to Section 2 - Installation.
6
Replace the control output printed circuit
board.
Refer to the instructions included with the
replacement part.
Table 9-15 Procedure #10—Troubleshooting current/time or time/current failure
symptoms
Step
What to do
How to do it or where to find the data
1
Be sure the recorder is configured for
current time/time current output.
Refer to Section 3 - Configuration. Make sure
OUT ALG selection = TI CUR or CUR TI.
2
Be sure all the recorder and control
related data is correct.
Refer to Section 3 - Configuration.
Check the tuning, algorithm, and control data.
3
Check that the applicable output relay
actuates properly. If it does, go to step 4.
If it does not check the field wiring; then
go to step 5.
Put the recorder into manual mode and adjust the
output manually to raise or lower the PV around
the setpoint. Listen for the click of the relay as the
PV moves in either direction. Observe OUT 1 or 2
indicator on the front display.
4
Check the control relay jumper positions.
Refer to Section 3 - Configuration.
5
Check the current proportional output.
Put the recorder in manual mode and manually
adjust the output from 0 to 100% (4–20 mA). Use
a milliammeter across the terminals in connector
J1 on the control output printed circuit board to
verify the output.
6
Recalibrate the current output.
Refer to Section 8 - Output Calibration.
7
Replace the control output printed circuit
board.
Refer to the instructions included with the
replacement part.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Honeywell DR4500A and is the answer not in the manual?

Honeywell DR4500A Specifications

General IconGeneral
BrandHoneywell
ModelDR4500A
CategoryRecording Equipment
LanguageEnglish

Related product manuals