EasyManua.ls Logo

Honeywell DR4500A - Entering the Setpoint Program Data

Honeywell DR4500A
266 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Setpoint Ramp/Soak Programming and Operation - Entering the Setpoint Program Data
Release M DR4500A Classic Series Circular Chart Recorder With or Without Control Product Manual 159
April 2017
6.4 Entering the Setpoint Program Data
Introduction
The procedure listed in Table 6-2 tells you what keys to press and what prompts you will see when entering
the setpoint program data. Follow the prompts in Sections 6.5, 6.6, and 6.7 when selecting the functions
for setpoint programming.
ATTENTION
Make sure SP RAMP and SP RATE are disabled first.
Table 6-2 Setpoint program data entry procedure
Step
Operation
Press
Action/Result
1
Select SP PROG Group
SET
UP
Until you see:
Upper Display: SET UP
Lower Display: SP RAMPn n = 1 or 2
2
Access SP PROG
FUNC
Until you see:
Upper Display: DISABL
Lower Display: SP PROG
If you see
Upper Display: ENABLE
Lower Display: SP RAMP
or
Upper Display: ENABLE
Lower Display: SP RATE
you must disable them; SP PROG and its subordinate
prompts are not visible unless SP RAMP and SP RATE
are disabled. Once they are disabled, press FUNC
until you see SP PROG.
3
Enable SP PROG
or
Until you see:
Upper Display: ENABLE
Lower Display: SP PROG
4
Select the functions
FUNC
Upper Display: shows current value for each prompt
Lower Display: shows individual function prompts within
the setpoint program group
Successive presses of the FUNCTION key
sequentially displays all the functions and their
values or selections.
Using the FUNCTION key, follow the prompts shown
in Sections 6.5, 6.6, and 6.7.

Table of Contents