Setpoint Ramp/Soak Programming and Operation - Entering the Setpoint Program Data 
Release M    DR4500A Classic Series Circular Chart Recorder With or Without Control Product Manual  159 
April 2017     
6.4  Entering the Setpoint Program Data 
Introduction 
The procedure listed in Table 6-2 tells you what keys to press and what prompts you will see when entering 
the setpoint program data.  Follow the prompts in Sections 6.5, 6.6, and 6.7 when selecting the functions 
for setpoint programming. 
 
Make sure SP RAMP and SP RATE are disabled first. 
 
Table 6-2 Setpoint program data entry procedure 
 
  Upper Display: SET UP 
  Lower Display: SP RAMPn  n = 1 or 2 
  Upper Display: DISABL 
  Lower Display: SP PROG 
If you see 
  Upper Display: ENABLE 
  Lower Display: SP RAMP 
or 
  Upper Display: ENABLE 
  Lower Display: SP RATE 
you must disable them; SP PROG and its subordinate 
prompts are not visible unless SP RAMP and SP RATE 
are disabled.  Once they are disabled, press FUNC 
until you see SP PROG. 
Until you see: 
  Upper Display: ENABLE 
  Lower Display: SP PROG 
Upper Display: shows current value for each prompt 
Lower Display: shows individual function prompts within 
the setpoint program group 
  Successive presses of the FUNCTION key 
sequentially displays all the functions and their 
values or selections. 
  Using the FUNCTION key, follow the prompts shown 
in Sections 6.5, 6.6, and 6.7.