Setpoint Ramp/Soak Programming and Operation - Setpoint Program Profiles Set Up Group
Release M DR4500A Classic Series Circular Chart Recorder With or Without Control Product Manual 163
April 2017
6.6 Setpoint Program Profiles Set Up Group
Introduction
You can configure up to six profiles; each profile contains a subset of the 36 segments. Each profile starts
with a ramp segment and ends with a soak segment. Each control loop uses one of these profiles. They can
use the same profile, too. The profiles can be synchronized to RUN/HOLD together.
Setpoint program profiles group prompts
Table 6-4 lists all the function prompts in the Setpoint Program Profiles setup group and their definitions.
Table 6-4 Setpoint program profiles group definitions
Lower Display
Prompt
Upper Display
Range of Setting or Selection
Parameter Definition
PRx STRT
RAMP1 RAMP 35
You can configure up to 6 profiles (PR1 PR6). Each
profile contains a subset of the 36 ramp and soak
segments configured later. PRx STRT designates the
number of the first segment of the profile. It must be a
ramp segment (odd number).
PRx END
SOAK2 SOAK36
This designates the number of the last segment of the
profile. It will be a soak segment (even number).
RAMPUNIT
TIME (Hours:Minutes)
EU/MIN (Engineering
Units/Minute)
EU/HR (Engineering Units/Hour)
This determines the engineering units for the ramp
segments.
SYNC 1+2
ENABLE
DISABL
Synchronizes the profiles for Control Loops 1 and 2.
This means that:
a) Both SP programs will RUN or HOLD
simultaneously.
b) A Guaranteed Soak Hold on one profile will cause
the other profile to HOLD for the duration of the
Guaranteed Soak Hold.