9.3 Self Diagnostics
Power-up tests
When the recorder is powered-up, four tests are run by the DR4500A software to ensure memory integrity.
As the tests are run, the displays appear as shown in Table 9-2.
Table 9-2 Power-up tests
Lower Display
Upper Display
RAM TEST
PASS or FAIL
CONFTEST (configuration checksum)
PASS or FAIL
CAL TEST (working calibration)
PASS or FAIL
BATTERY*
PASS or FAIL
*Battery test failure does not cause a failsafe.
Failsafe
If control is configured, and any testexcept BATTERY—fails, “FAIL” appears momentarily in the
upper display, then a display test is run, after which the controller goes into manual mode and you will
see:
Upper Display: (PV value)
Lower Display: FAILSAFE (blinking)
Refer to “Device Status” (next page) to determine which tests have failed and how to correct them.
All applicable error messages are displayed in rotation. If "CONTROL" is not configured, FAILSAFE
will not display. CNFG ERR, CAL1 ERR, CAL2 ERR, or BATT LOW will display, whether
FAILSAFE does or not.