Step 3 Set AI/DI_1 to Enable.
Step 4 Click Submit.
Step 5 Select Door sensor from the AI/DI_1 sensor type drop-down list box.
Figure 6-69 Setting a sensor type for a dry contact
Step 6 Click Unhide All Advanced Signals, then click Power Supply Parameters. Ensure
that III power supply enable(AIDI_1/DO) is Yes.
Step 7 Click Submit.
----End
6.5.2.1.2 Setting Smoke Sensor and Water Leakage Sensor Parameters on the
ECC800-Pro Web
After connecting a smoke sensor or water leakage sensor to the AI/DI port of an
ECC800-Pro collector, you need to set smoke sensor or water leakage sensor
parameters on the web user interface (WebUI) of the collector.
Prerequisites
You have obtained the IP address, and login user name and password for the
ECC800-Pro collector.
A PC with an IP address in the same network segment as the ECC800-Pro
collector is prepared, and the PC has been connected to the ECC800-Pro
collector over a switch.
Context
This section describes how to set smoke sensor or water leakage sensor
monitoring parameters when a smoke sensor or water leakage sensor is
connected to the AI/DI_1 port of the ECC800-Pro collector. Set the parameters
based on the actual port connected to the smoke sensor or water leakage
sensor onsite.
A smoke sensor or water leakage sensor is a
self-identication device. After a
smoke sensor or water leakage sensor is connected to the AI/DI port of an
ECC800-Pro collector, the sensor type is automatically
identied and you do
not need to manually set AI/DI_1 Sensor Type on the WebUI.
To enable automatic device
identication, choose System Settings > Device
Management > Device Addition > Auto Discover Device.
Procedure
Step 1 Log in to the WebUI of the ECC800-Pro collector.
Step 2 Choose Monitoring > System > ECC800 > Running Parameters > AI/DI_1 Port
Settings.
iMaster NetEco
Device Installation and Commissioning Guide (Data
Center) 6 Adding Devices
Issue 02 (2021-05-12) Copyright © Huawei Technologies Co., Ltd. 242

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Huawei iMaster NetEco V600R021C10 and is the answer not in the manual?

Huawei iMaster NetEco V600R021C10 Specifications

General IconGeneral
BrandHuawei
ModeliMaster NetEco V600R021C10
CategoryNetwork Hardware
LanguageEnglish

Related product manuals