Figure 6-19 Parallel Net Join Cong
System Settings Description
Alarm Parameters Select a device type, and check the alarm name, alarm
enabling, severity, and setting result.
Time Set the local time zone, date, and time.
IP Address Set the IP address, subnet mask, and default gateway
for the iBOX based on the IP address assigned by the
administrator.
Certicate
Management
Set the web security certicate, Modbus TCP certicate
management, Modbus TCP CA certicate management,
parallel communication certicate management, and
parallel communication CA certicate management
parameters.
Battery Curve Set the battery curve based on the battery brand and
model.
NetEco Select the NMS type and restore the default Modbus
TCP authentication password.
Parallel Net Join
Conguration
Information
Set this parameter when you connect iBOXs in parallel.
6.4.1.2 Creating an iBOX Collector on the NetEco
You can create an iBOX collector by manually creating the iBOX on the NetEco or
by adding a UPS for synchronizing the iBOX to the NetEco.
Prerequisites
● You have the operation rights for Planning
Conguration.
● You have created a management domain for the device to be added on the
Planning
Conguration page.
Context
The following operations describe how to manually create an iBOX.
● UPS_Huawei_UPS5000E_V1R3C00C01_MODBUSTCP
iMaster NetEco
Device Installation and Commissioning Guide (Data
Center) 6 Adding Devices
Issue 02 (2021-05-12) Copyright © Huawei Technologies Co., Ltd. 163