Follow-up Procedure
You can apply alarm redenition rules to alarms of the same type in batches:
1. Select the alarm rules to be applied to devices in batches.
– If you need to apply a specied alarm rule to the alarms of other devices
of the same type, select the data of the specied alarm rule in the
Redened Alarm list. Click Batch Apply to Devices. On the Batch Apply
to Devices page, select Selected for Selected Items.
– If you need to apply all alarm rules of the target device to alarms of
other devices of the same type, click Batch Apply to Devices. On the
Batch Apply to Devices page, select All for Selected Items.
2. Select the application scope of the device batch application.
– If you need to apply a
specied alarm rule of the target device to the
alarms of all devices of the same type, select All Objects for Application
scope.
– If you need to apply a
specied alarm rule of the target device to the
alarms of specied devices of the same type, select Custom for
Application scope and select the devices to which the alarm rule is to be
applied in the management domain area.
3. Click OK.
6.5.2.1.7 Modifying Performance Counter Names for Devices on the NetEco
This section describes how to modify device performance counter names on the
NetEco.
Prerequisites
● You have the operation rights for Planning
Conguration.
● You have created an ECC800-Pro collector in the Planning Conguration
page.
Procedure
Step 1 Log in to the NetEco client.
Step 2 On the main menu, choose Device Management > Conguration > Signal
Management.
Step 3 In the navigation pane on the left, select a device.
Step 4 Click the Sampling, Conguration, or Statistic tab and modify performance
counter names.
Step 5 Click Apply.
----End
6.5.2.2 Adding a Temperature and Humidity Sensor
iMaster NetEco
Device Installation and Commissioning Guide (Data
Center) 6 Adding Devices