Procedure
Step 1 Change the NetEco IP address.
1. In the browser address bar, enter https://client IP address of PowerEcho:31945,
enter the User Name and Password, and press Enter to access the
PowerEcho client.
The default user name for PowerEcho is admin and the preset password is
Changeme_123.
2. On PowerEcho, choose Maintenance > Network Conguration > Congure
IP Address from the main menu.
3. Choose Modify IP Address, select the NetEco to be
congured, and click Edit,
set IP Address,Subnet
Mask/Prex Length and NIC Usage, and click Apply.
After you change IP address of a database node, the product services and the databases
will be automatically restarted.
Step 2 Update the NetEco IP address on the ECC800-Pro WebUI.
1. Log in to the ECC800-Pro WebUI.
2. Set NetEco communications parameters.
Table 8-1 NetEco communications parameters
Path
Parameter Default
Value
Setting
System
Settings >
NMS
Application
> NetEco >
Communica
tion
Parameters
Server IP 192.168.8
.11
IP address of the primary NetEco
server
NOTE
The NetEco IP address and the
ECC800-Pro IP address must be
congured in the same network to
ensure normal connection between
the NetEco and the ECC800-Pro.
Port number 31220 31220
Network
port for link
setup
WAN_1 WAN_1 or WAN_2
3. Click Submit.
Step 3 Modify the UPS2000-G/UPS2000-H SNMP trap parameters (WebUI 1)
1. Log in to the UPS2000-G WebUI.
2. Choose System Settings > SNMP Settings.
3. In the SNMP Trap area, if Trap Target Address is the same as the NetEco IP
address before the
modication, select this row and click Delete.
4. In the SNMP Trap area, click Add.
iMaster NetEco
Device Installation and Commissioning Guide (Data
Center) 8 FAQ
Issue 02 (2021-05-12) Copyright © Huawei Technologies Co., Ltd. 322