Reader Shunt
The following RDR8S reader terminal input
points can be re-assigned:
Reader Door Contact
Reader REX
Reassignment of the special RDR8S reader terminal
output points to general purpose
output points is done by configuring the general purpose output points listed below:
Reader Output Point Terminal Output Point Number
Red LED Output 1 [Open Collector Output]
G
reen LED Output 2 [Open Collector Output]
Re
ader Shunt Output 3 [Relay Output]
Reader Strike Output 5 [Relay Output]
Reassignment of the special RDR8S reader input points to general purpose input
points is done by configuring the general purpose input points listed below:
Reader Input Point Terminal Input Point Number
Reader Door Sensor Input 1
Reader REX Input 2
NOTE
A write to flash must be performed after completion of input point/output
point disassociation configuration.