CK721-A User Interface CK721-A Installation and Operation
4-80 24-10349-8 Rev. B
This document contains confidential and proprietary information of Johnson Controls, Inc.
© 2012 Johnson Controls, Inc.
Activate Strike To g g le If enabled (Y), the door strike at the reader
initiating the event is activated. If multiple events
are executed from the same trigger and any
events have this flag set, the door will open.
If disabled (N),
a valid event invokes the event
action only, but does not unlock the door.
For legacy panels and badges with executive
pr
ivilege this setting does not apply. Also, events
with trigger type “Any Void Card” never unlock
the door.
Alarm Ack To g g le If enabled (Y),
the CK721-As alarm relay is
reset.
Input Group
En
able
Toggle If enabled (Y), an input group specified by the
Input Group field will be enabled.
Set Input
Su
ppression
Toggle Enable (Y) to suppress the specific Input Group
when this event is activated. Disable (N) to
unsuppress the specific Input Group when this
event is activated. When this event is
deactivated, the selected action is inverted: an
event that suppresses an input group on
activation, unsuppresses that input group on
deactivation; and an event that unsuppresses an
input group on activation, suppresses that input
group on deactivation.
Output Group User Def. Enter the number of an output group to activate
or
deactivate.
Input Group User Def. Enter the number of an input group to suppress
or
unsuppress.
Event Period User Def. Values range from 0 to 1440 minutes. If you set a
time value,
the event will deactivate on
expiration. Otherwise, the event will need to be
manually deactivated.
If the event activates an output group, the output
group will be deactivated
after this time period. If
the event suppresses an input group, the input
group will be unsuppressed after this time period.
Event Period applies only to event activation,
and not to event deactivation. Furthermore, only
output group activation and input group
suppression may be assigned a period, but not
output group deactivation and input group
unsuppression.
Table 4-29: Card Event Screen, Page 2
Field Type Description

Table of Contents

Other manuals for Johnson Controls CK721-A

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Johnson Controls CK721-A and is the answer not in the manual?

Johnson Controls CK721-A Specifications

General IconGeneral
BrandJohnson Controls
ModelCK721-A
CategoryController
LanguageEnglish

Related product manuals