12 Configuration
124
Continuation After the power failure, the program
continues to run from the point of dis-
ruption.
Start at actual value After the power failure, the program
continues to run from the current actual
value.
In the event of an error Continuation Program continues to run.
Program stop The time base of the program control-
ler is stopped.
Repetition No No program repeat
Yes -
Regulate last setpoint value No -
Yes Once the power is restored, the value
is set to the last setpoint value.
Start with power on No No automatic program start after power
on.
Yes Automatic program start after power
on.
Adopt temp. changes No Do not adopt temporary changes.
Yes Adopt temporary changes
Setpoint step No
Yes
Gradient unit Kelvin/minute
Kelvin/hour
Kelvin/day
Actual value input for tolerance
band monitoring
IN8 analog input 1 This value is monitored by the toler-
ance band.
Analog selector
Ö Chapter 12.6.8 "Ramp function",
page 99
Signal for actual value 2 IN8 analog input 1
Analog selector
Program tolerance band 0 to 9999 Determines the distance of the toler-
ance band around the program profile.
0 means switched off.
The set value monitors the actual value
input for tolerance band monitoring set
above and checks whether it is follow-
ing the program setpoint. If it leaves
the tolerance band, the program flow is
stopped until the actual value is back
within the tolerance band.
Program end time -1 to 0 to 9999 If -1 is entered, the program end time is
therefore infinite and the device does
not return to the operating loop. The
program end signal in the digital selec-
tor remains active until, for example,
another program is started.
Parameter Selection/settings Description