EasyManuals Logo

JUMO DICON touch User Manual

JUMO DICON touch
196 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #25 background imageLoading...
Page #25 background image
25
4 Electrical connection
4.2 Galvanic isolation
Voltage supply
AC/DC 24 V
Analog output
Relay outputs
RS422/485
Ethernet, PROFINET
Digital 1input
Analog IN11input
Analog input IN8
DC 50 V
AC 30 V
»
1 solid state relay output
AC 230 V, 1 A
AC 3600 V
»
Voltage supply
AC 240 V
1 l
DC 0/22 V, max. 30 mA
(short-circuit proof)
ogic output
2 logic outputs
DC 0/12 V, max. 20 mA
(short-circuit proof)
Digital input
(potential free
contact)
7
DC 50 V
AC 30 V
»
DC 50 V
AC 30 V
»
DC 50 V
AC 30 V
»
AC 3600 V
»
AC 3600 V
»
AC 3600 V
»
DC 50 V
AC 30 V
»
DC 50 V
AC 30 V
»
2 PhotoMOS® solid state relay
U = DC 45 V, I = 200 mA
max. max.
U = AC 30 V, I = 200 mA
max. max.
DC 50 V
AC 30 V
»
»
USB
(host, device)
PROFIBUS
DC 50 V
AC 30 V
»
2 solid state relay outputs
AC 230 V, 1 A
for controlling motor actuators
AC 3600 V
»
»

Table of Contents

Other manuals for JUMO DICON touch

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the JUMO DICON touch and is the answer not in the manual?

JUMO DICON touch Specifications

General IconGeneral
BrandJUMO
ModelDICON touch
CategoryController
LanguageEnglish

Related product manuals