12 Configuration
12.6.5 Control loop monitoring
Control loop monitoring monitors the control response during startup of a plant and in the event
of a setpoint step by analyzing the change of the actual value during an output level change.
An alarm is issued if the actual value does not respond according to the specifications.
The alarm signal is available from the digital selector and can be processed further at any time.
Setup dialog box
Parameters
Parameter Selection/settings Description
Function
&
Inactive Control loop monitoring is generally not permitted
Active Control loop monitoring is generally permitted
Response time 0 to 1999 Time period in which the actual value must leave the
monitoring band.
"0 s" setting means:
Response time = reset time Tn
Monitoring band 0.0000 to 1999 Width of the monitoring band that the actual value must
leave within the response time
"0" setting means:
Monitoring band = 0.5 × proportional band (Xp)