NICE1000
new
User Manual Troubleshooting
- 183 -
Fault
Code
Name Possible Causes Solution Level
Err26
Earthquake
signal
101: The earthquake signal
is active and the duration
exceeds 2s.
101: Check that the earthquake
signal is consistent with the
parameter setting (NC, NO) of the
MCB.
3B
Err29
Shorting
PMSM stator
feedback
abnormal
101: The shorting PMSM
stator feedback is
abnormal.
101:
Check that the state (NO, NC)
of the feedback contact on the
contactor is correct.
Check that the contactor
and corresponding feedback
contact act correctly.
Check the coil circuit of
the shorting PMSM stator
contactor.
5A
Err30
Elevator
position
abnormal
101, 102:
In the normal-speed running
or re-leveling running mode,
the running time is larger
than the value of F9-02, but
the leveling signal has no
change.
101, 102:
Check whether the leveling
signal cables are connected
reliably and whether the signal
copper wires may touch the
ground or be short circuited
with other signal cables.
Check whether the distance
between two oors is too large,
causing too long re-leveling
running time.
Check whether signal loss
exists in the encoder circuits.
4A
Err33
Elevator speed
abnormal
101: The detected running
speed during normal-speed
running exceeds the limit.
102: The speed exceeds
the limit during inspection
or shaft auto-tuning.
103: The speed exceeds
the limit in shorting stator
braking mode.
104: The speed exceeds
the limit during emergency
running.
105: The emergency
running time protection
function is enabled (set
in Bit8 of F6-69), and the
running time exceeds 50s,
causing the timeout fault.
101:
Check whether the encoder is
used properly.
Check the setting of motor
nameplate parameters.
Perform motor auto-tuning
again.
102: Attempt to decrease the
inspection speed or perform
motor auto-tuning again.
103: Check whether the shorting
PMSM stator function is enabled.
104, 105:
Check whether the emergency
power capacity meets the
requirements.
Check whether the emergency
running speed is set properly.
5A