- 184 -
Fault
Code
Name Possible Causes Solution Level
Err34 Logic fault
Logic of the MCB is
abnormal.
Contact the agent or Monarch. 5A
Err35
Shaft auto-
tuning data
abnormal
101: When shaft auto-
tuning is started, the
elevator is not at the bottom
oor or the down slow-down
is invalid,
102: The system is not
in the inspection state
when shaft auto-tuning is
performed.
103: It is judged upon
power-on that shaft auto-
tuning is not performed.
104: In distance control
mode, it is judged at running
startup that shaft auto-
tuning is not performed.
106, 107, 109, 114: The
plate pulse length sensed
at up/down leveling is
abnormal.
108, 110: No leveling signal
is received within 45s
continuous running.
111, 115: The stored oor
height is smaller than 50
cm.
112: The oor when auto-
tuning is completed is not
the top oor.
113: The pulse check is
abnormal.
101: Check that the down slow-
down switch is valid, and that F4-
01 (Current oor) is set to 1.
102: Check that the inspection
switch is in inspection state.
103, 104:
Perform shat auto-tuning.
106, 107, 109, 114:
•
Check that NO/NC setting
of the leveling sensor is set
correctly
•
Check whether the leveling
plates are inserted properly
and whether there is strong
power interference if the
leveling sensor signal blinks.
•
Check whether the leveling
plate is too long for the
asynchronous motor.
108, 110:
Check whether the running times
out: No leveling signal is received
when the running time exceeds
F9-02.
111, 115:
Enable the super short oor
function if the oor distance
is less than 50 cm. If the oor
distance is normal, check
installation of the leveling plate for
this oor and check the sensor.
112: Check whether the setting of
F6-00 (Top oor of the elevator) is
smaller than the actual condition.
113: Check whether the signal
of the leveling sensor is normal.
Perform shaft auto-tuning again.
4C